| Plan Review Notes For Permit 15051084 |
| Permit Number |
15051084 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-23 13:25:02 | PLAN DENIED | | | 1) PLEASE EXPLAIN WHAT AHU- 1 IS COOLING HALLWAY OR | | | CLEAN ROOM | | | 2) PROVIDE A ENGINEER DETAIL ON CONDENSER STAND TIED TO | | | ROOF | | | AND CONDENSER TIED TO STAND. PROVIDE TYPE AND SIZE | | | ANCHOR USED. | | | PER SECTION 301.12 WIND RESISTANCE FBC (M) 2010 | | | 3) PROVIDE HEATING AND COOLING CALCULATIONS. PER | | | SECTION | | | 503.2.1 FLORIDA ENERGY CODE 2010. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|