| 2015-05-29 07:04:17 | 1) INDICATE ON THE APPLICATION IF THE LP TANK IS |
| | COVERED UNDER THIS PERMIT. THE APPLICATION ONLY STATES |
| | "1000 AG DISPENSER." |
| | 2) THE SITE PLAN SHOWS A FENCED IN AREA. IS THIS AREA |
| | RELATED TO THE DISPENSING OF THE LP GAS OR RELATED |
| | EQUIPMENT? CLARIFY. |
| | 3) THERE ARE NOTES ON THE SITE PLAN THAT ARE DONE IN |
| | PENCIL.PENCILED NOTES ARE UNACCEPTABLE AS THEY CAN BE |
| | CHANGED. ANY NOTES SHALL BE DONE IN INK. |
| | 4) I AM QUESTIONING THE VALUE OF $2400 FOR THIS JOB, |
| | ESPECIALLY IF THE TANK IS INCLUDED.SUBMIT A DETAILED |
| | ESTIMATE OR BONA FIDE SIGNED CONTRACT FOR THE WORK. WPB |
| | AMEND. TO 2010 FBC SEC. 109.3. |
| | 5) SUBMIT DETAILS FOR THE BOLLARDS. SHOW THE DIAMETER, |
| | MATERIAL, SPACING, OF THE BOLLARDS, DEPTH OF THE POSTS |
| | BELOW GROUND AND THE DISTANCE ABOVEGROUND. COMPLY WITH |
| | FL. ADMIN. CODE RULE 5J-20.045 (C). |
| | 6) SHOW THE LOCATION OF THE REQUIRED SIGNAGE PER THE |
| | FL. ADMIN. RULE SEC.5J-20.045 (1). |
| | 7) THE ANCHORAGE PLANS SHALL BE SIGNED AND SEALED BY |
| | R.F. TUCKER PER THE FLA. ADMIN. CODE RULE 61G15-23.002. |
| | 8) INDICATE THE LENGTH OF THE EARTH ANCHORS THAT WILL |
| | BE USED TO COMPLY WITH 170 MPH WIND LOAD. |
| | 9) ONE OF THE SPEC SHEETS FOR THE LP TANK HAS PART OF |
| | THE NOTES CUT OFF ON ONE SIDE.SUBMIT CLEAN COPIES,WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 10) INDICATE ON THE PLAN THE TYPE OF FOUNDATION THE LP |
| | TANK IS RESTING UPON.WPB AMEND. TO 2010 FBC 107.2.1. |
| | 11) SUBMIT MANUF. SPEC SHEETS FOR THE DISPENSER AND |
| | SHOW ANY ASSOCIATED PIPING TO THE DISPENSER. |
| | |