| Plan Review Notes For Permit 15051048 |
| Permit Number |
15051048 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-09 16:56:27 | 1) THE PLANS NOTE THE SCOPE OF PLUMBING WORK TO ADD A | | | WASHING MACHINE AND A TANKLESS WATER HEATER. THERE IS | | | NO TANKLESS WATER HEATER OR WASHING MACHINE SHOWN ON | | | THE PLANS. CLARIFY. | | | 2) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. | | | TO 2010 FBC SEC. 107.3.5.1.3. | | | 3) THE PLANS SHOW THE OCCUPANCY AS MERCANTILE. INDICATE | | | ON THE PLANS WHAT WILL BE SOLD. THE PLANS SHOW A NEW | | | PREP TABLE. WILL THERE BE ANY TYPE OF FOOD PREPARATION | | | OR COOKING DONE ON THE PREMISES? INDICATE ON THE | | | PLANS.WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 4) A GREASE REMOVAL DEVICE MAY BE REQUIRED DEPENDENT | | | UPON THE TYPE OF GOODS BEING PREPARED. SUBMIT | | | CALCULATIONS FOR A GREASE TRAP/ INTERCEPTOR IN | | | ACCORDANCE WITH FBC-PLUMBING SEC.1003.3.1. | | | 5) THE NEW HAND SINK IS SHOWN CONNECTING TO AN EXISTING | | | 2" STACK. UPON RESEARCH OF CITY RECORDS, THIS STACK | | | APPEARS TO BE AN EXISTING 3"STACK. REVISE. | | | 6) SINCE THIS IS A MULTI-STORY BUILDING, THE USE OF A | | | AIR ADMITTANCE VALVE ON THE MOP SINK WILL REQUIRE A | | | RELIEF VENT IN ACCORDANCE WITH 2010 FBC-PLUMBING | | | SEC.917.3.2 OR REVISE THE DESIGN TO A STACK & VENT | | | SYSTEM. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|