Plan Review Notes
Plan Review Notes For Permit 15051037
Permit Number 15051037
Review Stop B
Sequence Number 2
Notes
Date Text
2015-07-07 15:59:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051037
 ADD: 1701 S. FLAGLER DR. SUITE # 402
 CONT: TIM JOHNSON REMODELING, INC.
 TEL: (561)832-7331
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 07/ 2015
 ACTION: DENIED
  
 1) COMPLIED. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS: MISSING FLOOR PLAN
 SHOWING THE LOCATION OF THIS SUITE IN RELATION TO THE
 WHOLE FLOORAS WELL AS THE OPENINGS WITH IN THE SUITE.
 THE LOCATION OF THE UNIT AND OPENINGS IS IMPORTANT IN
 DETRERMINING IF THEY ARE LOCATED IN A WALL ZONE
 4(INTERIOR ZONE) OR A WALL ZONE 5 (AN END WALL ZONE
 WITH HIGHER ASSOCATED PRESSURES).
  
 2) INFORMATIONAL!!!!THIS BUILDING IS A HIGH-RISE OF
 APPROX. 200 FEET IN HEIGHT AND AN EXPOSURE D. THE
 PRESSURES WILL NEED TO BE COMPLETED BY A FLORIDA
 LICENSED P. E. DESIGNED TO ASCE &-10.
  
 3) SEMI-COMPLIED. THE WIND DESIGN CRITERIA IS NOT
 LISTED ON THE PLANS AS TO HOW THE PRESSURES WERE
 ACHIEVED. , MISSING THE WIND DESIGN CRITERIA. WIND
 DESIGN CRITERIA 2010 FBC-B 1609.1.1 DETERMINATION OF
 WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 2ND REQUEST. 4) HIGHLIGHT, CIRCLE THE SIZE OF OPENINGS,
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLIONS, FASTENERS TO
 BE INSTALLED AND ASSOCIATED PRESSURES.
  
 2ND REQUEST. 5) CONTRACTOR TO SUBMIT PRODUCT APPROVALS.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  