| Date |
Text |
| 2015-06-22 10:01:46 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15051037 |
| | ADD: 1701 S. FLAGLER DR. SUITE # 402 |
| | CONT: TIM JOHNSON REMODELING, INC. |
| | TEL: (561)832-7331 |
| | E-MAIL:[email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON.JUNE 22/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: MISSING FLOOR PLAN |
| | SHOWING THE LOCATION OF THIS SUITE IN RELATION TO THE |
| | WHOLE FLOORAS WELL AS THE OPENINGS WITH IN THE SUITE. |
| | THE LOCATION OF THE UNIT AND OPENINGS IS IMPORTANT IN |
| | DETRERMINING IF THEY ARE LOCATED IN A WALL ZONE |
| | 4(INTERIOR ZONE) OR A WALL ZONE 5 (AN END WALL ZONE |
| | WITH HIGHER ASSOCATED PRESSURES). |
| | |
| | 2) THIS BUILDING IS A HIGH-RISE OF APPROX. 200 FEET IN |
| | HEIGHT AND AN EXPOSURE D. THE PRESSURES WILL NEED TO BE |
| | COMPLETED BY A FLORIDA LICENSED P. E. DESIGNED TO ASCE |
| | &-10. |
| | |
| | 3) MISSING THE WIND DESIGN CRITERIA. WIND DESIGN |
| | CRITERIA 2010 FBC-B 1609.1.1 DETERMINATION OF WIND |
| | DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 3.2AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 4) HIGHLIGHT, CIRCLE THE SIZE OF OPENINGS, WIDTH & |
| | HEIGHT, TYPE OF GLAZING, MULLIONS, FASTENERS TO BE |
| | INSTALLED AND ASSOCIATED PRESSURES. |
| | |
| | 5) CONTRACTOR TO SUBMIT PRODUCT APPROVALS. 2010 FBC |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |