Plan Review Notes
Plan Review Notes For Permit 15051024
Permit Number 15051024
Review Stop G
Sequence Number 1
Notes
Date Text
2015-06-20 07:19:391) SUBMIT MANUF. SPECS. FOR THE POOL HEATERS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SUBMIT A GAS RISER DIAGRAM. SHOW THE LENGTH OF ALL
 CUT SECTIONS OF PIPE, TYPE OF PIPING MATERIAL BEING
 INSTALLED, SIZES, TYPE OF GAS, AND THE BTU LOAD OF EACH
 APPLIANCE/ PIECE OF EQUIPMENT.
 3) SHOW THE TOTAL DEVELOPED LENGTH FROM THE POINT OF
 DELIVERY TO POOL HEATERS.
 4) INDICATE THE DELIVERY PRESSURE ( PSI) OF THE FUEL
 GAS. 2010 FGC SEC. 402.2.
 5) THE POOL HEATERS SHALL COMPLY WITH THE 2010 FL.
 ENERGY CODE SEC.504.7 & TABLE 504.2. THERMAL EFFICIENCY
 OF 78% FOR UNITS MANUFACTURED PRIOR TO 4/16/13 AND 82%
 FOR UNITS MANUFACTURED AFTER 4/16/13.
 6) SUBMIT THE GAS TABLE FROM THE 2010 FGC THAT WAS USED
 FOR SIZING THE SYSTEM. FGC SEC. 402.2.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  