| Plan Review Notes For Permit 15051024 |
| Permit Number |
15051024 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-20 07:19:39 | 1) SUBMIT MANUF. SPECS. FOR THE POOL HEATERS. WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) SUBMIT A GAS RISER DIAGRAM. SHOW THE LENGTH OF ALL | | | CUT SECTIONS OF PIPE, TYPE OF PIPING MATERIAL BEING | | | INSTALLED, SIZES, TYPE OF GAS, AND THE BTU LOAD OF EACH | | | APPLIANCE/ PIECE OF EQUIPMENT. | | | 3) SHOW THE TOTAL DEVELOPED LENGTH FROM THE POINT OF | | | DELIVERY TO POOL HEATERS. | | | 4) INDICATE THE DELIVERY PRESSURE ( PSI) OF THE FUEL | | | GAS. 2010 FGC SEC. 402.2. | | | 5) THE POOL HEATERS SHALL COMPLY WITH THE 2010 FL. | | | ENERGY CODE SEC.504.7 & TABLE 504.2. THERMAL EFFICIENCY | | | OF 78% FOR UNITS MANUFACTURED PRIOR TO 4/16/13 AND 82% | | | FOR UNITS MANUFACTURED AFTER 4/16/13. | | | 6) SUBMIT THE GAS TABLE FROM THE 2010 FGC THAT WAS USED | | | FOR SIZING THE SYSTEM. FGC SEC. 402.2. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|