| Plan Review Notes For Permit 15051022 |
| Permit Number |
15051022 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-10-01 09:29:39 | NONE OF THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS HAVE | | | BEEN ADDRESSED FROM THE REVIEW DONE ON 8/10/15. | | | 1) SHOW THE SPACING BETWEEN THE FLOOR INLETS AND | | | ADJACENT WALL. SPACING SHALL NOT EXCEED 10 FEET PER | | | 2010 FBC SEC.424.1.6.5.9.4. 2ND REQUEST. | | | 2) INDICATE ON THE PLAN HOW WATER WILL BE SUPPLIED TO | | | THE AQUATIC ACCESS LIFT.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SHT. 1 OF 5 SHOWS THE POOL WATER DRAINING TO THE | | | SANITARY SYSTEM.POOL WATER CANNOT DRAIN TO THE SANITARY | | | SYSTEM OR TO THE STORM WATER SYSTEM PER CITY ORDINANCE | | | SEC.90-126 (5). PLEASE CONTACT MANNY GONZALEZ IN THE | | | CWPB ENGINEERING DEPT. 561-494-1040 FOR FURTHER | | | DIRECTION. | | | 4) THE POOL HEATERS SHALL COMPLY WITH THE 2010 | | | FBC-ENERGY TABLE 504.2 & SHALL HAVE A THERMAL | | | EFFICIENCY OF 82% AND COMPLY WITH ASHRAE 146. SUBMIT | | | CONFIRMATION OF COMPLIANCE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|