2015-10-01 09:29:39NONE OF THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS HAVE
 BEEN ADDRESSED FROM THE REVIEW DONE ON 8/10/15.
 1) SHOW THE SPACING BETWEEN THE FLOOR INLETS AND
 ADJACENT WALL. SPACING SHALL NOT EXCEED 10 FEET PER
 2010 FBC SEC.424.1.6.5.9.4. 2ND REQUEST.
 2) INDICATE ON THE PLAN HOW WATER WILL BE SUPPLIED TO
 THE AQUATIC ACCESS LIFT.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. 1 OF 5 SHOWS THE POOL WATER DRAINING TO THE
 SANITARY SYSTEM.POOL WATER CANNOT DRAIN TO THE SANITARY
 SYSTEM OR TO THE STORM WATER SYSTEM PER CITY ORDINANCE
 SEC.90-126 (5). PLEASE CONTACT MANNY GONZALEZ IN THE
 CWPB ENGINEERING DEPT. 561-494-1040 FOR FURTHER
 DIRECTION.
 4) THE POOL HEATERS SHALL COMPLY WITH THE 2010
 FBC-ENERGY TABLE 504.2 & SHALL HAVE A THERMAL
 EFFICIENCY OF 82% AND COMPLY WITH ASHRAE 146. SUBMIT
 CONFIRMATION OF COMPLIANCE.
  