Plan Review Notes
Plan Review Notes For Permit 15051022
Permit Number 15051022
Review Stop E
Sequence Number 3
Notes
Date Text
2015-10-23 11:11:54THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
  
 THE PREVIOUS REVIEW MENTIONED REQUIREMENTS STATED ON
 THE PLANS INITIALLY SUBMITTED FOR PERMITTING. THESE
 PLANS THOUGH INCLUDE A GENERIC RISER DIAGRAM AND
 CONDUCTOR SIZING SCHEDULE, CLEARLY STATE THAT A
 LICENSED ELECTRICAL CONTRACTOR IS TO PROVIDE ACCURATE
 LOAD CALCS, FEEDER SCHEDULES, PANEL SCHEDULES AND ALL
 DATA ASSOCIATED WITH THIS INSTALLATION. FURTHERMORE, AS
 I INDICATED IN THE PREVIOUS REVIEW COMMENTS, WHAT IS
 BEING DONE ABOUT THE SITE LIGHTING FOR THIS AREA? IS
 THE LIGHTING ALREADY IN PLACE? IF SO, INDICATE THAT
 OTHERWISE SITE LIGHTING DRAWINGS SHALL BE PROVIDED.
 THESE SHALL COMPLY WITH THE FBC-ENERGY CONSERVATION
 CODE. THE SCOPE OF THE PERMIT SHALL BE CLEARLY DEFINED
 TO INCLUDE ALL OF THE PROPOSED WORK.
 YOU NEED TO SUBMIT SITE PLANS SHOWING THE LOCATION OF
 THE MAIN DISCONNECT, AND THE LOCATION OF ANY AND ALL
 EQUIPMENT ASSOCIATED WITH THIS PERMIT. YOU WILL HAVE TO
 PROVIDE A DIAGRAM OF THE PROPOSED EQUIPMENT RACK IF
 ANY. SUBMIT LOAD CALCS AND A PANEL SCHEDULE. WHO WILL
 BE RESPONSIBLE FOR THE EQUI-POTENTIAL BONDING?
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  