Plan Review Notes
Plan Review Notes For Permit 15051022
Permit Number 15051022
Review Stop B
Sequence Number 3
Notes
Date Text
2015-10-01 17:08:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051022
 ADD: 1517 CAMERON SAMUELS LANE
 CONT: A& G CONCRETE POOLS, INC
 TEL: ( 772)878-7752
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
  
 NOTICE!!!!!!!!!!!!!!!!!!!!!!!!!: CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
  
  
 3RD REVIEW
 DATE: THURS. OCT. 01/2015
 ACTION: DENIED
  
 1) 3RD REVIEW ONLY ONE SET OF AQUATIC ACCESS SALES
 BROCHURE WAS SUBMITTED. COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE CAN NOT BE DETERMINED PLEASE
 SHOW COMPLIANCE WITH:
 2010 FBC-ACCESSIBILITY COCE;
  
 1009.2.2 SEAT LOCATION OK
 .
 1009.2.4 SEAT HEIGHT THE LOW HEIGHT RANGE DOES NOT MEET
 THE REQUIREMENT OF 16 INCHES.
  
 1009.2.5 SEAT WIDTH OK
  
 1009.2.6 FOOT REST AND ARMREST DOES NOT INDICATE CODE
 COMPLIANCE. FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE
 WITH THE SEAT. IF PROVIDED, THE ARMREST POSITIONED
 OPPOSITE THE WATER SHALL BE REMOVABLE OR SHALL FOLD
 CLEAR OF THE SEAT WHEN THE SEAT IS IN THE RAISED (LOAD)
 POSITION.
  
 1009.2.7 OPERATION POOL LIFTS MUST BE CAPABLE OF
 UNASSISTED OPERATION FROM BOTH THE DECK AND WATER
 LEVELS. THIS WILL PERMIT A PERSON TO CALL THE POOL LIFT
 WHEN THE POOL LIFT IS IN THE OPPOSITE POSITION. IT IS
 EXTREMELY IMPORTANT FOR A PERSON WHO IS SWIMMING ALONE
 TO BE ABLE TO CALL THE POOL LIFT WHEN IT IS IN THE UP
 POSITION SO HE OR SHE WILL NOT BE STRANDED IN THE WATER
 FOR EXTENDED PERIODS OF TIME AWAITING ASSISTANCE. THE
 REQUIREMENT FOR A POOL LIFT TO BE INDEPENDENTLY
 OPERABLE DOES NOT PRECLUDE ASSISTANCE FROM BEING
 PROVIDED.
  
 1009.2.8 SUBMERGED DEPTH. OK
  
 1009.2.9 LIFTING CAPACITY. SINGLE PERSON POOL LIFTS
 MUST BE CAPABLE OF SUPPORTING A MINIMUM WEIGHT OF 300
 POUNDS (136 KG) AND SUSTAINING A STATIC LOAD OF AT
 LEAST ONE AND A HALF TIMES THE RATED LOAD. POOL LIFTS
 SHOULD BE PROVIDED THAT MEET THE NEEDS OF THE
 POPULATION THEY SERVE. PROVIDING A POOL LIFT WITH A
 WEIGHT CAPACITY GREATER THAN 300 POUNDS (136 KG) MAY BE
 ADVISABLE.
  
 2) COMPLIED SOLAR BLANKET.
  
 3) PUT YOUR PLANS AND SUBMITTALS TOGETHER IN 2
 PACKAGES!!!!!!!! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  