| Plan Review Notes For Permit 15051022 |
| Permit Number |
15051022 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-09-17 11:15:29 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. PER NOTE ON PAGE 5, THE FEED TO THE AQUAWORX PANEL | | | IS BEING PERFORMED BY THE EC (ELECTRICAL CONTRACTOR) | | | UNDER A SEPARATE PERMIT. THAT WOULD EXCLUDE THE | | | EQUIPOTENTIAL BONDING, POOL AND SITE LIGHTING IN | | | ADDITION TO INCIDENTAL ELECTRICAL WORK REQUIRED. | | | ACCORDING TO THE ELECTRICAL DRAWINGS, THE SCOPE | | | TERMINATES AT THE POOL EQUIPMENT DISCONNECT. | | | 2. PROVIDE DETAIL OF AQUAWORX EQUIPMENT WITH LOAD CALCS | | | TO EQUIPMENT DISCONNECT. | | | 3. YOU SHALL INDICATE THE EC FOR THE REMAINDER OF THE | | | WORK AS DESCRIBED ABOVE. | | | 4. AREA LIGHTING SHALL COMPLY WITH THE FBC-E SECTION | | | 505. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | | | | | | | |
|