Plan Review Notes
Plan Review Notes For Permit 15051022
Permit Number 15051022
Review Stop E
Sequence Number 2
Notes
Date Text
2015-09-17 11:15:29PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PER NOTE ON PAGE 5, THE FEED TO THE AQUAWORX PANEL
 IS BEING PERFORMED BY THE EC (ELECTRICAL CONTRACTOR)
 UNDER A SEPARATE PERMIT. THAT WOULD EXCLUDE THE
 EQUIPOTENTIAL BONDING, POOL AND SITE LIGHTING IN
 ADDITION TO INCIDENTAL ELECTRICAL WORK REQUIRED.
 ACCORDING TO THE ELECTRICAL DRAWINGS, THE SCOPE
 TERMINATES AT THE POOL EQUIPMENT DISCONNECT.
 2. PROVIDE DETAIL OF AQUAWORX EQUIPMENT WITH LOAD CALCS
 TO EQUIPMENT DISCONNECT.
 3. YOU SHALL INDICATE THE EC FOR THE REMAINDER OF THE
 WORK AS DESCRIBED ABOVE.
 4. AREA LIGHTING SHALL COMPLY WITH THE FBC-E SECTION
 505.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
  
  