Plan Review Notes
Plan Review Notes For Permit 15051022
Permit Number 15051022
Review Stop P
Sequence Number 1
Notes
Date Text
2015-06-01 14:24:361) SUBMIT MANUF. SPECS. FOR THE WHEELCHAIR LIFT. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT. 1 OF 5 SHOWS THE 3" WASTE LINE DISCHARGING TO
 THE STORM DRAINAGE SYSTEM.ONLY STORMWATER SHALL DRAIN
 TO THE STORM DRAINAGE SYSTEM PER CITY ORDINANCE SEC. 90
 - 203.
 3) SHOW THE SPACING BETWEEN THE FLOOR INLETS AND
 ADJACENT WALL. SPACING SHALL NOT EXCEED 10 FEET PER
 2010 FBC SEC.424.1.6.5.9.4.
 4) A BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED AT
 THE CITY METER.CONTACT STEPHEN HUNTER IN THE CWPB
 UTILITIES AT 561-822-2242 FOR TYPE OF BFP DEVICE
 REQUIRED. MINIMUM PROTECTION SHALL BE A REDUCED
 PRESSURE ZONE (RPZ) TYPE DEVICE.
 5) SUBMIT MANUF. SPECS. FOR THE POOL HEATERS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 6) SUBMIT PIPING DETAILS FOR THE POOL HEATERS. DETAILS
 SHALL INCLUDE VALVES, THERMOMETER, PIPE SIZES, AND
 MATERIAL SPECIFICATIONS PER THE 2010 FBC SEC.
 424.1.6.5..14.
 7) SUBMIT VERIFICATION THAT THE MAXIMUM FILTRATION RATE
 OF 2 GPM PER SQUARE FOOT OF FILTER AREA IS NOT
 EXCEEDED. FBC 424.1.6.5.5.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  