| Plan Review Notes For Permit 15051022 |
| Permit Number |
15051022 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-01 14:24:36 | 1) SUBMIT MANUF. SPECS. FOR THE WHEELCHAIR LIFT. WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) SHT. 1 OF 5 SHOWS THE 3" WASTE LINE DISCHARGING TO | | | THE STORM DRAINAGE SYSTEM.ONLY STORMWATER SHALL DRAIN | | | TO THE STORM DRAINAGE SYSTEM PER CITY ORDINANCE SEC. 90 | | | - 203. | | | 3) SHOW THE SPACING BETWEEN THE FLOOR INLETS AND | | | ADJACENT WALL. SPACING SHALL NOT EXCEED 10 FEET PER | | | 2010 FBC SEC.424.1.6.5.9.4. | | | 4) A BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED AT | | | THE CITY METER.CONTACT STEPHEN HUNTER IN THE CWPB | | | UTILITIES AT 561-822-2242 FOR TYPE OF BFP DEVICE | | | REQUIRED. MINIMUM PROTECTION SHALL BE A REDUCED | | | PRESSURE ZONE (RPZ) TYPE DEVICE. | | | 5) SUBMIT MANUF. SPECS. FOR THE POOL HEATERS. WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 6) SUBMIT PIPING DETAILS FOR THE POOL HEATERS. DETAILS | | | SHALL INCLUDE VALVES, THERMOMETER, PIPE SIZES, AND | | | MATERIAL SPECIFICATIONS PER THE 2010 FBC SEC. | | | 424.1.6.5..14. | | | 7) SUBMIT VERIFICATION THAT THE MAXIMUM FILTRATION RATE | | | OF 2 GPM PER SQUARE FOOT OF FILTER AREA IS NOT | | | EXCEEDED. FBC 424.1.6.5.5.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|