Plan Review Notes
Plan Review Notes For Permit 15051022
Permit Number 15051022
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-06 14:18:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051022
 ADD: 1517 CAMERON SAMUELS LANE
 CONT: A& G CONCRETE POOLS, INC
 TEL: ( 772)878-7752
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JUNE 06/2015
 ACTION: DENIED
  
 1) SHEET 1 INDICATES THE USE OF A BATTERY OPERATED
 HANDICAPPED CHAIRLIFT. PLEASE PROVIDE THE MANUFACTURERS
 SPECS ON THIS PRODUCT AND FOR THE INSTALATION OF THE
 LIFT. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET 1 INDICATES THE USE OF (3) POOL HEATERS.
 PLEASE PROVIDE CODE COMPLIANCE WITH 2010 FBC-ENERGY
 CODE 504.7.3 HEATED SWIMMING POOLS AND INGROUND
 PERMANENTLY INSTALLED SPAS SHALL BE EQUIPED WITH A
 VAPOR RETARDANT COVER ON THE WATER OR AT THE WATER
 SURFACE OR A LIQUID COVER OR OTHER MEANS PROVEN TO
 REDUCE HEAT LOSS.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  