| 2015-06-24 15:39:54 | 6/24/2015 |
| | PROJECT: CONDO RENNOVATION |
| | PERMIT#: 15051008 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) NOTE 8 CALLS FOR NEW LED LIGHTING IN A NEW SOFFIT. |
| | 1A) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE |
| | PROPOSED LED LIGHTING INDICATING COMPLIANCE WITH NEC |
| | 110.3 AND NEC 410 |
| | 1B) INDICATE HOW THE NEW LIGHTING IS TO BE CONTROLED. |
| | |
| | 2) NOTE 10 INDICATES A NEW RECEPATACLE TO BE INSTALLED. |
| | 2A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW |
| | RECEPTACLE ASSOCIATED WITH NOTE 10. NEC 210.52 |
| | 2B) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 3) NOTE 12 CALLS FOR A NEW GROUND FAULT OUTLET. |
| | 3A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW |
| | RECEPTACLE ASSOCIATED WITH NOTE 12. NEC 210.8 |
| | |
| | 4) NOTE 13 CALLS FOR THE INSTALLATION OF NEW SMOKE |
| | DETECTORS. |
| | 4A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW SMOKE |
| | DETECTORS ASSOCIATED WITH NOTE 13. FBC-R 314, 315 |
| | 4B) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315. |
| | |
| | 5) NOTE 16 CALL FOR THE INSTALLATION OF NEW RECESSED |
| | LIGHTING. |
| | 5A) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE |
| | PROPOSED RECESSED LIGHTING INDICATING COMPLIANCE WITH |
| | NEC 110.3 AND NEC 410 |
| | 5B) RECESSED LUMINAIRES INSTALLED IN THE BUILDING |
| | THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| | UNCONDITIONED SPACES. FBC-E 502.3.8 |
| | |
| | 6) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE |
| | PROPOSED MIRROR LIGHTING INDICATING COMPLIANCE WITH NEC |
| | 110.3 AND NEC 410 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |