Plan Review Notes For Permit 15051008
Permit Number 15051008
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-24 15:39:546/24/2015
 PROJECT: CONDO RENNOVATION
 PERMIT#: 15051008
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) NOTE 8 CALLS FOR NEW LED LIGHTING IN A NEW SOFFIT.
 1A) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE
 PROPOSED LED LIGHTING INDICATING COMPLIANCE WITH NEC
 110.3 AND NEC 410
 1B) INDICATE HOW THE NEW LIGHTING IS TO BE CONTROLED.
  
 2) NOTE 10 INDICATES A NEW RECEPATACLE TO BE INSTALLED.
 2A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW
 RECEPTACLE ASSOCIATED WITH NOTE 10. NEC 210.52
 2B) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) NOTE 12 CALLS FOR A NEW GROUND FAULT OUTLET.
 3A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW
 RECEPTACLE ASSOCIATED WITH NOTE 12. NEC 210.8
  
 4) NOTE 13 CALLS FOR THE INSTALLATION OF NEW SMOKE
 DETECTORS.
 4A) INDICATE ON THE PLAN THE LOCATION FOR THE NEW SMOKE
 DETECTORS ASSOCIATED WITH NOTE 13. FBC-R 314, 315
 4B) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 5) NOTE 16 CALL FOR THE INSTALLATION OF NEW RECESSED
 LIGHTING.
 5A) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE
 PROPOSED RECESSED LIGHTING INDICATING COMPLIANCE WITH
 NEC 110.3 AND NEC 410
 5B) RECESSED LUMINAIRES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 UNCONDITIONED SPACES. FBC-E 502.3.8
  
 6) PROVIDE MANUFACTURER PRODUCT CT SHEETS FOR THE
 PROPOSED MIRROR LIGHTING INDICATING COMPLIANCE WITH NEC
 110.3 AND NEC 410
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  