Plan Review Notes
Plan Review Notes For Permit 15051008
Permit Number 15051008
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-11 06:32:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051008
 ADD: 1801 S FLAGLER DR SUITE # 1709
 CONT: ARTISAN DESIGN & CONSTRUCT
 TEL: (954)364-8544
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 11/2015
 ACTION: DENIED
  
 1) SHEET A1.01 SHOWS NEW WOOD AND TILE FLOORS BEING
 INSTALLED IN VARIOUS ROOMS OF THE SUITE. LEASE PROVIDE
 TESTING REPORTS FOR THE FLOOR INSULATION THAT COMPLIES
 WITH THE (3) FOLLOWINGS CODE SECTIONS:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) BATHROOM LABELED ROOM 003 SHOWS A NEW SHOWER
 ENCLOSURE, PLEASE PROVIDE THE TYPE OF BACKING BOARD
 THAT WILL BE INSTALLED IN THE SHOWER ENCLOSURE AND
 CEILING ABOVE, SHOW COMPLIANCE WITH 2010 FBC-B 2509.2
 BASE FOR TILE & 2509.3 LIMITATIONS.
  
 3) SHEET A1.01 NOTE # 8 INDICATES NEW SOFFITS, PLEASE
 PROVIDE A DETAIL SHOWING THE FRAMING TYPE & SIZE,
 SPACING, ATTACHMENT TO WALL & DECK ABOVE, AND THE TYPE
 OF FINISH MATERIAL AND THICKNESS.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FORCOMMERCIAL
 BUILDINGS. STRUCTURAL ELEMENTS.
  
 4) SHEET A1.01 NOTES INDICATE THE REPLACEMENT OF
 EXTERIOR WINDOW AND SLIDDING GLASS DOORS. SHEET A2.02
 PROVIDES WIND PRESSURES BUT THERE IS NO WIND DESIGN
 CRITERIA TO BASE THESE PRESSURES ON? NOTE IF THIS SUITE
 IS LOCATED IN A ZONE 4 OR ZONE 5.
  
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH ASCE 7-10 NOTE: HIGHRISE OF 200 FT.
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM ASCE 7-10. EXPOSURE D
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE ASCE 7-10.
  
 5) ON THE PRODUCT APPROVALS. PLEASE CIRCLE THE
 FOLLOWING INFORMATION. THE WIDTH & HEIGHT OF THE UNIT,
 TYPE OF GLAZING IF THERE IS OPTIONS, SILL HEIGHT OF
 SLIDDING GLASS DOOR UNITS, MULLIONS, RE-INFORCED OR
 NOT, HEIGHT AND WIDTH OF TRIBUTARY AREA, AND AMOUNT OF
 ANCHORS PER END PLATE AND TYPE OF ANCHORS TO BE
 INSTALLED. WITHOUT THIS INFORMATION A REVIEW CAN NOT
 TAKE PLACE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED TO DETERMINE CODE COMPLIANCE.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved