| 2016-03-02 13:44:01 | 3/2/16 FAILED ELECTRICAL REVIEW AS NOTED. PLANS |
| | REVIEWED UNDER 15030466. CP, LEM & SAK NOTIFIED VIA |
| | EMAIL. MA |
| | 1. THE ROUTING OF THE SERVICES MAY REQUIRE THAT AN |
| | EASEMENT BE RECORDED PER UNIT. IF SO, THESE WILL HAVE |
| | TO BE FILED AND RECORDED PRIOR TO FINAL INSPECTIONS. |
| | THIS WILL BE DETERMINED AND NOTED ON THE ELECTRICAL |
| | SITE PLAN. TYPICAL |
| | 2. FBC?E SECTION 404.1 REQUIRES THAT A MINIMUM OF 50 OF |
| | THE LAMPS IN PERMANENTLY INSTALLED LUMINAIRES BE HIGH |
| | EFFICIENCY LAMPS. TYPICAL |
| | 3. NEC 314.27(A) REQUIRES THAT BOXES IN CEILING FOR |
| | LUMINAIRES BE LISTED TO SUPPORT A MINIMUM OF 50LBS. |
| | TYPICAL |
| | 4. NEC 314.27(D) STATES THAT OUTLET BOXES INTENDED FOR |
| | THE SOLE SUPPORT OF PADDLE FANS BE LISTED AND MARKED BY |
| | THE MANUFACTURER FOR THE PURPOSE. TYPICAL |
| | 5. NEC 210.52(C)1 STATES THAT EVERY COUNTER SPACE |
| | GREATER THAN 12? SHALL BE AN OUTLET. |
| | 6. THERE SHOULD BE LIGHTING CONTROL (4WAY SWITCH) FOR |
| | CORRIDOR LIGHT AT ENTRANCE TO REAR BEDROOM. |
| | 7. THE SWITCH FOR THE ATTIC LIGHT SHOULD BE MOUNTED IN |
| | A VISIBLE LOCATION AND BE PROVIDED WITH A PILOT LIGHT |
| | TO INDICATE WHEN LIGHT IS EITHER ON OR OFF. |
| | 8. RELOCATE SMOKE DETECTORS SO THEY ARE NO LESS THAN |
| | 36? FROM THE TIP OF A PADDLE FAN BLADE. TYPICAL |
| | 9. FBC?E402.4.5 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. TYPICAL |
| | 10. ADJUST THE ELECTRICAL LEGEND SO THE DISCONNECT |
| | SYMBOL MATCHES THAT USED ON THE FLOOR PLAN (TYPICAL) |
| | |