| Plan Review Notes For Permit 15050980 |
| Permit Number |
15050980 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-03 14:04:22 | FAILED ELECTRICAL REVIEW AS NOTED BELOW. | | | | | | 1. NEC 410.16(B) PROHIBITS THE USE OF THE TRADITIONAL | | | PORCELAIN PULL CHAIN FIXTURES IN CLOSETS. USE A | | | SUITABLE WALL SWITCHED LUMINAIRE. | | | 2. NEC 210.70(C) REQUIRES THAT THE SWITCH BE AT THE | | | USUAL POINT OF ENTRY. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] |
|