| Plan Review Notes For Permit 15050974 |
| Permit Number |
15050974 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-06-03 14:06:25 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDINGS ON THE | | | PLANS OR APPLICATION. FBC 107.2.1 | | | | | | 2) SPECIFY THE SQUARE FOOTAGE OF THE TWO ROOF AREAS. | | | FBC 107.2.1 | | | | | | 3) THE MAXIMUM DESIGN PRESSURE FOR THE W-6 SYSTEM ON | | | PAGE 3 OF THE TARCO MODIFIED BITUMEN ROOF SYSTEM (FL | | | 9487 - R2) IS - 75.0 PSF. NOTE #5 ON PAGE 1 DOES NOT | | | ALLOW RATIONAL ANALYSIS TO INCREASE THE DESIGN PRESSURE | | | FOR THIS SYSTEM. THE REQUIRED ROOF UPLIFT PRESSURES FOR | | | A STRUCTURE WITH A FLAT ROOF AND A MEAN ROOF HEIGHT OF | | | 15' OR LESS LOCATED IN EXPOSURE CATEGORY "C" WITH A 170 | | | MPH VULTIMATE WIND SPEED ARE -37.9 PSF IN ROOF ZONE 1, | | | -63.6 PSF IN ROOF ZONE 2 AND -95.7 PSF IN ROOF ZONE 3. | | | THE PROPOSED ROOF SYSTEM DOES NOT HAVE ADEQUATE DESIGN | | | PRESSURE FOR ROOF ZONE 3. FBC-R 301.2.1 | | | | | | 4) THE VALUE FOR THE WORK WAS SPECIFIED AS $7000.00 ON | | | THE ORIGINAL APPLICATION AND THE VALUE ON THE NEW | | | APPLICATION IS $6000.00. CLARIFY. FBC 109.3 |
|