2015-06-03 14:06:25PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDINGS ON THE
 PLANS OR APPLICATION. FBC 107.2.1
  
 2) SPECIFY THE SQUARE FOOTAGE OF THE TWO ROOF AREAS.
 FBC 107.2.1
  
 3) THE MAXIMUM DESIGN PRESSURE FOR THE W-6 SYSTEM ON
 PAGE 3 OF THE TARCO MODIFIED BITUMEN ROOF SYSTEM (FL
 9487 - R2) IS - 75.0 PSF. NOTE #5 ON PAGE 1 DOES NOT
 ALLOW RATIONAL ANALYSIS TO INCREASE THE DESIGN PRESSURE
 FOR THIS SYSTEM. THE REQUIRED ROOF UPLIFT PRESSURES FOR
 A STRUCTURE WITH A FLAT ROOF AND A MEAN ROOF HEIGHT OF
 15' OR LESS LOCATED IN EXPOSURE CATEGORY "C" WITH A 170
 MPH VULTIMATE WIND SPEED ARE -37.9 PSF IN ROOF ZONE 1,
 -63.6 PSF IN ROOF ZONE 2 AND -95.7 PSF IN ROOF ZONE 3.
 THE PROPOSED ROOF SYSTEM DOES NOT HAVE ADEQUATE DESIGN
 PRESSURE FOR ROOF ZONE 3. FBC-R 301.2.1
  
 4) THE VALUE FOR THE WORK WAS SPECIFIED AS $7000.00 ON
 THE ORIGINAL APPLICATION AND THE VALUE ON THE NEW
 APPLICATION IS $6000.00. CLARIFY. FBC 109.3