| 2015-07-30 10:43:24 | FBC 2010 2ND REVUEW | | | | | | PROVISIONALLY APPROVED AS FOLLOWS: | | | | | | PROVIDE REVISION FOR: | | | | | | FBC-R M1305.1.3 APPLIANCES IN ATTICS. | | | ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN | | | OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE | | | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT | | | NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES | | | (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG | | | MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM | | | THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE | | | CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 | | | NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE | | | SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES | | | (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE | | | APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS | | | OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY | | | 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW | | | REMOVAL OF THE LARGEST APPLIANCE. | | | | | | FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS. | | | A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE | | | REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN | | | ACCORDANCE WITH CHAPTER 34. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | |
|