| Plan Review Notes For Permit 15050961 |
| Permit Number |
15050961 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-17 14:28:34 | 1ST REVIEW: FBC 2010 | | | | | | THE MECHANICAL PLAN IS TOO SMALL TO READ. THE SIZING | | | CALCULATION IS DIFFICULT TO READ. PROVIDE THE EQUIPMENT | | | SCHEDULE AND LEGIBLE SIZING CALCUATION SUCH THAT PROPER | | | SIZING MAY BE DETERMINED. THE SCHEDULE PROVIDED DOES | | | NOT INCLUDE CAPACITY. THE SIZING CALCULATION DOES NOT | | | LIST EQUIPMENT. | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|