Plan Review Notes
Plan Review Notes For Permit 15050961
Permit Number 15050961
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-17 14:28:341ST REVIEW: FBC 2010
  
 THE MECHANICAL PLAN IS TOO SMALL TO READ. THE SIZING
 CALCULATION IS DIFFICULT TO READ. PROVIDE THE EQUIPMENT
 SCHEDULE AND LEGIBLE SIZING CALCUATION SUCH THAT PROPER
 SIZING MAY BE DETERMINED. THE SCHEDULE PROVIDED DOES
 NOT INCLUDE CAPACITY. THE SIZING CALCULATION DOES NOT
 LIST EQUIPMENT.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER