2015-06-29 20:39:15APPROVED WITH THE FOLLOWING NOTATIONS:1
 IMPORTANT NOTICE:
 IN ADDITION TO THE REQUIRED DISCONNECT, LUMINAIRE
 W/SWITCH BY THE ENTRY AND THE SERVICE OUTLET FOR THE
 AHU INSIDE THE ATTIC. NEC 110.34 ALSO STATES THAT A
 PERMANENT LADDER OR STAIRWAY SHALL BE PROVIDED TO GIVE
 SAVE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED IN ATTICS.
 CEILING LUMINAIRE OUTLETS SHALL;L SUPPORT 50# PER NEC
 314.27
 INSTALL INTER-SYSTEM BONDING TERMINAL AS IN NEC 250.94
 FEEDER TO EXISTING 60A PANEL SHALL NOT BE W/NM CABLE AS
 IT IS NOT LISTED FOR WET LOCATIONS NEC 300.5(B)
 ALL NEW DEVICES SHALL BE TAMPER-RESISTANT AS IN NEC
 406.11
  
  