| Plan Review Notes For Permit 15050961 |
| Permit Number |
15050961 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-29 20:39:15 | APPROVED WITH THE FOLLOWING NOTATIONS:1 | | | IMPORTANT NOTICE: | | | IN ADDITION TO THE REQUIRED DISCONNECT, LUMINAIRE | | | W/SWITCH BY THE ENTRY AND THE SERVICE OUTLET FOR THE | | | AHU INSIDE THE ATTIC. NEC 110.34 ALSO STATES THAT A | | | PERMANENT LADDER OR STAIRWAY SHALL BE PROVIDED TO GIVE | | | SAVE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL | | | EQUIPMENT INSTALLED IN ATTICS. | | | CEILING LUMINAIRE OUTLETS SHALL;L SUPPORT 50# PER NEC | | | 314.27 | | | INSTALL INTER-SYSTEM BONDING TERMINAL AS IN NEC 250.94 | | | FEEDER TO EXISTING 60A PANEL SHALL NOT BE W/NM CABLE AS | | | IT IS NOT LISTED FOR WET LOCATIONS NEC 300.5(B) | | | ALL NEW DEVICES SHALL BE TAMPER-RESISTANT AS IN NEC | | | 406.11 | | | | | | |
|