| Plan Review Notes For Permit 15050960 |
| Permit Number |
15050960 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-02 09:51:41 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- IF THE SUPPLY DUCT FOR BEDROOM #2 IS 8", THEN THE 9" | | | TRANSFER DUCT SIZE DOESN'T COMPLY WITH THE BALANCE | | | RETURN AIR SEC. M1602.4 OF 2010 FBC-RESIDENTIAL. | | | | | | NOTE: THE APPROVED PLANS SHOWED 7" SUPPLY DUCT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|