2015-06-02 09:51:41RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- IF THE SUPPLY DUCT FOR BEDROOM #2 IS 8", THEN THE 9"
 TRANSFER DUCT SIZE DOESN'T COMPLY WITH THE BALANCE
 RETURN AIR SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 NOTE: THE APPROVED PLANS SHOWED 7" SUPPLY DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]