| Notes |
| Date |
Text |
| 2015-06-02 08:35:31 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- A/C PLAN DOESN'T SHOW THE SIZE OF SUPPLY DUCT FOR | | | BEDROOM #2. UNABLE TO VERIFY IF THE TRANSFER DUCT SIZE | | | SHOWN IS IN COMPLIANCE WITH THE BALANCE RETURN AIR SEC. | | | M1602.4 OF 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|