2015-06-02 08:35:31RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- A/C PLAN DOESN'T SHOW THE SIZE OF SUPPLY DUCT FOR
 BEDROOM #2. UNABLE TO VERIFY IF THE TRANSFER DUCT SIZE
 SHOWN IS IN COMPLIANCE WITH THE BALANCE RETURN AIR SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL.
  