Plan Review Notes
Plan Review Notes For Permit 15050951
Permit Number 15050951
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-27 09:55:49****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 A FLOOR PLAN SHOWING WINDOW TYPES, SIZES, AND LOCATIONS
 WAS NOT PROVIDED.
  
 THIS PERMIT IS ISSUED WITH PROVISO THAT BEDROOM WINDOWS
 MEET THE SIZE REQUIREMENTS OF FBC 2010 RESIDENTIAL 310
 FOR EMERGENCY ESCAPE AND RESCUE.
  
 IF ANY OF THE BEDROOMS DO NOT HAVE A COMPLIANT OPENING,
 A REVISION WHICH SHOWS COMPLIANCE WITH FBC 2010
 EXISTING BUILDING 604.1 (5% REDUCTION) IS REQUIRED.
 REVISION TO INCLUDE CALCUATIONS TO SHOW COMPLIANCE.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved