| 2015-10-22 19:39:18 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE FBC, |
| | (FLORIDA BUILDING CODE) 2010, AS APPLICABLE AND BELOW |
| | ARE THE DEFICIENCIES NOTED. |
| | 1. GENERAL NOTES REFERENCE TO THE 2010 NEC SHALL BE |
| | CORRECTED AS IT NEVER EXISTED. THE APPLICABLE CODE FOR |
| | THIS PROJECT IS THE 2008 EDITION. |
| | 2. THE SHEET INDEX MAKES REFERENCE TO SHEET E1.0 FOR |
| | THE ELECTRIC WHICH IS NOT PROVIDED, YET SUBMITTED SHEET |
| | E2.1 IS NOT MENTIONED. CORRECT ACCORDINGLY. |
| | 3. PER NEC 210.70)(A) EXCEPTION AUTOMATIC LIGHTING |
| | CONTROL IS REQUIRED FOR THE EXTERIOR STAIRWAYS. |
| | 4. THE WORD ?ROMEX? AS USED IN NOTE 26.3 IS TO IDENTIFY |
| | A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE |
| | OF CABLE; REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?. |
| | 5. NOTE 26.4 DICTATES KITCHEN COUNTER SPACING AT 36? |
| | CENTER CONTRARY TO NEC 210.52(C) REQUIREMENTS. CORRECT |
| | NOTE ACCORDINGLY. |
| | 6. SMOKE DETECTOR IS REQUIRED INSIDE THE GARAGE |
| | APARTMENT. |
| | 7. ARC-FAULT PROTECTION IS ERRONEOUSLY ONLY ADDRESSED |
| | FOR SMOKE DETECTOR CIRCUITS ON THE PLANS. ARC-FAULT |
| | PROTECTION REQUIREMENTS APPEAR IN NEC 210.12. |
| | 8. ALL DWELLING RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT ?TR? PER NEC 406.11. |
| | 9. ALL OUTLETS IN WET LOCATIONS SHALL BE LISTED |
| | WEATHER-RESISTANT ?WR? AS INDICATED IN NEC 406.8. |
| | 10. ALL CEILING OUTLET BOXES SHALL BE LISTED TO SUPPORT |
| | 50#?S AS PER NEC 314.27. |
| | 11. DWELLING UNIT RECEPTACLES SHALL BE SPACED AS |
| | INSTRUCTED IN NEC 210.52. AS SUCH YOU ARE MISSING |
| | OUTLETS IN THE FAMILY ROOM, BEHIND THE FIREPLACE, |
| | LIVING ROOM, BEDROOMS I & II. |
| | 12. PORCH LIGHT SHALL BE CONTROLLED VIA A 3 WAY SWITCH |
| | BY ENTRY WAY. |
| | 13. BEDROOM CORRIDOR SHALL BE PROPERLY ILLUMINATED AND |
| | SWITCHED PREFERABLY WITH A 3 OR 4 WAY SWITCHES. |
| | 14. IF THE OUTLET INSIDE THE CLOSET IN BEDROOM II IS TO |
| | BE INTENDED FOR THE CONNECTION OF ANY EQUIPMENT, NEC |
| | 210.70 REQUIRES THAT THERE BE A LIGHT CONTROLLED BY A |
| | WALL SWITCH FOR THAT ROOM. |
| | 15. KITCHEN COUNTER OR PENINSULA OUTLETS SHALL BE AS |
| | DICTATED IN NEC 210.52 (C); THE PENINSULA SHALL HAVE AN |
| | OUTLET AS REQUIRED. |
| | 16. THERE SHALL BE A GFI ?WR? OUTLET IN FRONT OF THE |
| | DWELLING PER NEC 210.52(E)(1). |
| | 17. YOU SHALL SHOW THE REQUIRED LAUNDRY CIRCUIT 19 ON |
| | THE FLOOR PLAN. |
| | 18. YOU SHALL PROVIDE ACCURATE AND SITE SPECIFIC FEEDER |
| | DIAGRAM AND LOAD CALCS SHOW PROPER CONDUCTOR AND GROUND |
| | CONDUCTOR SIZING FOR THE COMPLETE SERVICE AS MANDATED |
| | BY NEC 215.5. |
| | 19. THE CONNECTED LOAD AS INDICATED EXCEEDS THE RATING |
| | OF THE MAIN CIRCUIT BREAKER AND BUS BAR OF PANEL P1. |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |
| | |