| Plan Review Notes For Permit 15050879 |
| Permit Number |
15050879 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-11 13:26:47 | 2ND REVIEW: FBC 2010 | | | | | | FBC 107 _ PROVIDE AN ENERGY SUBMITTAL. | | | FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW | | | SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R | | | M15. | | | PROVIDE AN EQUIPMENT SCHEDULE. | | | FBC-EC 403.2.5 PROVIDE A SIZING CALCULATION | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|