| Date |
Text |
| 2015-07-14 12:51:04 | 7/14/2015 |
| | PROJECT: 347 PLYMOTH |
| | PERMIT#: 15050879 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) THE SERVICE RISER PROVIDE IS NOT COMPLIANT. |
| | DISCONNECTS SHALL BE GROUPED. NEC 230.72. YOU INDICATE |
| | PANEL P1 TO BE LOCATED INSIDE MAIN HOUSE NEW LAUNDRY |
| | ROOM AND P2 TO BE LOCATED IN THE DETACHED GARAGE |
| | BUILDING. |
| | |
| | 2) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE |
| | METER. |
| | |
| | 3) INDICATE THE SIZE AND CONTENTS OF THE EXISTING |
| | SERVICE RACEWAY BETWEEN THE METER AND PANEL P1. YOUR |
| | NOTES 26.1 ON PAGE E-2.1 INDICATE THAT YOU PROPOSE A |
| | NEW ELECTRICAL SERVICE WITH MAIN DISCONNECT THIS |
| | CONFLICTS WITH YOUR RISER DIAGRAM. |
| | CLARIFIFICATION REQUIRED. YOU INDICATE THE METER AND |
| | SERVICE ENTRANCE CONDUCTORS TO PANEL P1 ARE EXISTING |
| | AND YET PANEL P1 IS A NEW PANEL AND ACCORDING TO PAGE |
| | A-1.0 IT IS IN A NEW LOCATION. |
| | YOU ALSO INDICATE PANEL P2 IS FED THROUGH P1 HOWEVER |
| | THERE IS NO INDICATION OF AN OCPD IN PANEL P1 TO FEED |
| | P2. IN ADDITION THE NOTES ON PAGE E-2.1 INDICATE A NEW |
| | UNDERGROUND TO THE EXISTING SERVICE. THERFORE THE |
| | SERVICE RISER AND SITE/FLOOR PLAN NEED CLARIFICATION. |
| | |
| | 4) INDICATE ALL REQUIRED SMOKE DETECTORS. YOU HAVE |
| | INDICATED SMOKE DETECTORS OUTSIDE OF THE SLEEPING ROOMS |
| | BUT NOT INSIDE. ALSO GIVE CAREFUL CONSIDERATION TO THE |
| | REQUIREMENTS IN THE FBC-R 315 CARBON MONOXIDE |
| | DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-RESIDENTIAL 314 AND 315. |
| | |
| | 5) PROVIDE CLARIFICATION AT THE ELECTRICAL PANEL. EVERY |
| | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. NEC 408.4 SPECIFICALLY THE WATER HEATER |
| | IN BOTH PANELS. THE SYSTEM VOLTAGE AND LOAD SHOULD BE |
| | CLEAR. YOU HAVE INDICATED THE WIRE SIZE AND IN MOST |
| | CASES THE NUMBER OF POLES USED BUT THE OCPD SIZE HAS |
| | NOT BEEN INDICATED. PLEASE CLARIFY. |
| | |
| | 6) PROVIDE DISCONNECTS AT AHU'S NEC 440.14 |
| | |
| | 7) INDICATE GFI AS GEQUIRED IN THE KITCHEN FOR |
| | COUNTERTOP OUTLETS. NEC 210.8(6) |
| | |
| | 8) VERIFY CLEARANCES REQUIRED FOR ELECTRICAL PANEL AND |
| | ELECTRICAL EQUIPMENT REQUIRING SERVICE. NEC 110.26 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| 2015-07-11 13:26:23 | 2ND REVIEW: FBC 2010 |
| | |
| | UNDER REVIEW - SENT TO DAVID HAYES |
| | |
| | |