| 2015-07-11 13:26:07 | 2ND REVIEW: FBC 2010 |
| | |
| | NEW COMMENTS: |
| | |
| | PROVIDE DETAILS FOR EACH SET OF THE NEW STAIRS, |
| | LANDINGS, AND HANDRAILS. |
| | |
| | EXPLAIN TO WHICH PART OF THE BUILDING THE WALL SECTION |
| | ON SHEET A-1.2 APPLIES. |
| | |
| | FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY |
| | SUBMITTAL. |
| | |
| | THE PROJECT QUALIFIES AS A RENOVATION AS THE PROPOSED |
| | COST EXCEEDS 30% OF THE VALUE OF THE EXISTING |
| | STRICTURE. |
| | |
| | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| | STORIES. |
| | |
| | FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | PREVIOUS COMMENTS: |
| | |
| | PROVIDE STRUCTURAL DETAILS FOR ALTERATIONS OF OPENINGS |
| | TO ACCOMODATE THE INSTALLATION OF NEW WINDOW AND DOOR |
| | PRODUCTS, AS MAY BE NECESSARY. |
| | |
| | ADDITIONALLY, THE PLAN NOTES ARE IN CONFLICT WITH THE |
| | PRODUCT APPROVALS AND NOTE 08.1 & 08.2 ON SHEET A-1.1 |
| | INDICATING IMPACT RESISTANT WINDOWS, SPECIFYING NON |
| | IMPACT, AND ALSO PROVIDING STORM PANELS. PLEASE FURTHER |
| | EVALUATE THESE ISSUES AND SPECFY WHAT IS SPECIFICALLY |
| | PROPOSED. |
| | |
| | THE DESIGN PRESSURES PROVIDED SHOULD BE SPECIFIC TO |
| | EACH OPENING. YOU HAVE APPARENTLY PROVIDED A ONLY |
| | GENERAL ZONE INFORMATION. |
| | |
| | |
| | |
| | |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |