| Plan Review Notes For Permit 15050879 |
| Permit Number |
15050879 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-04 06:43:17 | 1ST REVIEW: FBC 2010 | | | | | | FBC 107 PLEASE PROVIDE ADDITIONAL DETAILS AS FOLLOWS: | | | | | | STRUCTURAL DETAIL FOR ALTERATIONS OF OPENINGS TO | | | ACCOMODATE THE INSTALLATION OF NEW WINDOW AND DOOR | | | PRODUCTS, AS MAY BE NECESSARY. | | | | | | THE ARCHITECTS LETTER OF 4/17/15 INDICATES FL 15227-68M | | | WILL BE USED AS AN EXTERIOR SWING DOOR. THE PROVIDED | | | DOOR PRODUCT INFORMATION IS BY A MANUFACTURER | | | INCONSISTENT WITH THE ONE FOUND UNDER THIS NUMBER AT | | | HTTPS://FLORIDABUILDING.ORG/PR/PR_DEFAULT.ASPX | | | | | | THE ARCHITECTS LETTER OF 4/17/15 INDICATES FL 13578-R1 | | | WILL BE USED FOR STEEL SHUTTERS. THE PRODUCT | | | INFORMATION IS NOT PROVIDED. | | | | | | NOTE: IT MAY BE ADVISABLE FOR THE DESIGNER OR A | | | CONSULTANT ENGINEER TO REVIEW THE WINDOW AND DOOR | | | PRODUCTS FURTHER AND PROVIDE ADDITION ANALYSIS AS TO | | | DESIGN PRESSURES AND TO PROVIDE AN INSTALLATION | | | SCHEDULE FOR THE SHUTTERS. | | | YOU MAY WISH TO UTILIZE THE SCHEDULE FOUND AT: HTTP://W | | | PB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/2013/09/ | | | SCHEDULE_FOR_INSTALLATION.PDF | | | | | | PLEASE INDICATE THE METHOD INTENDED FOR COMPLIANCE WITH | | | FBC-R311.1 AS TO EGRESS WHEN THE BUILDING IS SHUTTERED. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|