| Plan Review Notes For Permit 15050862 |
| Permit Number |
15050862 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-26 09:40:50 | RE-ROOF AND RECOVER BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- TAS 126 MOISTURE TESTING IS MISSING THE ROOF | | | MOISTURE SURVEY SHOWING LOCATION AND RESULTS OF ALL | | | TESTS PERFORMED. SEC. 14 OF TAS 125-95. | | | | | | 2- NOA 13-0219.14 SUBMITTED FOR THE ROOF SYSTEM OVER | | | RECOVERY DECKS EXPIRED ON 08/31/14. NEED TO PROVIDE | | | CURRENT NOA. DCA RULE 9N-3. | | | | | | 3- ENGINEER TO REVISE ALL CALCULATIONS TO MATCH NEW | | | NOA. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|