| 2015-06-02 11:08:32 | 2ND REVIEW: FBC 2010 |
| | |
| | SUBMIT AN ADEQUATE PLAN AS PREVIOUSLY NOTED. PERHAPS |
| | YOU SHOULD CONSIDER HAVING AN ENGINEERED DESIGN. YOUR |
| | DESIGN INDICATES A 12" WIDE FOOTING WITH AN 8" BLOCK |
| | WALL AND ONLY #5 IN THE FOOTING. YOU INDICATE THE WALL |
| | WILL RETAIN SOMETHING, BUT YOU DO NOT IDENTIFY WHAT IS |
| | WILL RETAIN. WHAT IS THE RELATIONSHIP OF THE FOOTING |
| | DEPTH TO THE FINALA GRADE, AND THE HEIGHT OF WALL TO |
| | FINAL GRADE? IS DIRT BEING RETAINED? WILL A 12" WIDE |
| | FOOTING RESIST THE MOMENT IMPOSED ON IT BY RETAINED |
| | DIRT ON POSSIBLY ONLY ONE SIDE? |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |