| 2015-06-01 09:40:00 | 1ST REVIEW: FBC 2010 | | | | | | FAILED MINIMUN PLAN REVIEW FBC 107. | | | | | | PROVIDE DETAILS FOR THE PROPOSED RETAINING WALL, SHOW | | | WALL HEIGTH, FOOTING DIMENSIONS, FOOTING STEEL | | | PLACEMENT, COLUMN STEEL PLACEMENT, BEAM STEEL | | | PLACEMENT. PROXIMITY OF WALL TO PROPERTY LINES, ANY | | | INCORPORATED DRAINAGE DESIGN OR AFFECT ON DRAINAGE | | | CONDITIONS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|