| 2015-06-16 14:40:23 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | 1. AS PER NEC 110.16, PANELS SHALL BE MARKED WITH THE |
| | REQUIRED ARC-FLASH PROTECTION WARNING LABEL. |
| | 2. AS PER NEC 210.8(B)(5), ALL 125 V, 15 ? 20 AMP |
| | OUTLETS WITHIN 6? OF A SINK SHALL BE GFI PROTECTED. |
| | 3. AS PER NEC 230.8, ALL UNDERGROUND SERVICE RACEWAYS |
| | SHALL BE SEALED TO AVOID MOISTURE ETC. AS PER NEC |
| | 300.5. |
| | 4. AS PER NEC 230.95, THREE PHASE WYE SERVICES OF 1000 |
| | AMPS OR GREATER REQUIRE GFI PROTECTION. |
| | 5. AS PER NEC 300.7, RACEWAYS EXPOSED TO DIFFERENT |
| | TEMPERATURES ENVIRONMENTS SHALL BE SEALED TO AVOID THE |
| | TRANSFER WARM AIR INTO THE COLD SPACE, |
| | 6. AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE |
| | GFI PROTECTED. |
| | 7. AS PER NEC 700.12, YOU SHALL INDICATE THE CIRCUIT |
| | NUMBER SERVING EACH EMERGENCY LIGHT TO ASCERTAIN |
| | COMPLIANCE IN THAT THEY HAVE TO BE ON THE SAME LIGHTING |
| | CIRCUIT AS THE AREA THEY OCCUPY. |
| | 8. AS PER NEC 760.4, THE CIRCUIT SUPPLYING THE FACP |
| | SHALL BE LABELED AND IDENTIFIED ACCORDINGLY. |
| | 9. FBC-ENERGY CONSERVATION, AMONG OTHER REQUIREMENTS, |
| | ALL LIGHTING SHALL COMPLY WITH SECTION 505 OF THIS |
| | CODE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, OR I CAN BE OF FURTHER |
| | ASSISTANCE, PLEASE DO NOT HESITATE TO CONTACT ME. |
| | |