| Plan Review Notes For Permit 15050807 |
| Permit Number |
15050807 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-28 19:00:32 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE WIND DESIGN DATA ON THE DRAWINGS. | | | | | | 2) SPECIFY THE DIMENSIONS OF THE POURED CONCRETE | | | COLUMNS ON THE DRAWINGS. | | | | | | 3) THE MAXIMUM HEIGHT OF THE COLUMNS IS SPECIFIED AS | | | 3.5' (3'-6") ON SHEET H1 AND 3'-9" ON SHEET H2. | | | CLARIFY. FBC 107.2.1 |
|