| Plan Review Notes For Permit 15050705 |
| Permit Number |
15050705 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-02 15:36:30 | APPROVED AS NOTED BELOW: | | | IMPORTANT NOTICE: | | | 1. PROPER GROUND COVER OVER RACEWAYS & CONDUCTOR | | | INSULATION AS INDICATED IN NEC 300.5 WILL BE REQUIRED & | | | VERIFIED. NO SITE TUBES FOR TRENCH INSPECTION | | | 2. GROUNDING ELECTRODE CONDUCTOR PER NEC 250.66 (#4) | | | 3. INTER-SYSTEM BONDING TERMINAL PER NEC 250.94 | | | 4. GROUNDING ELECTRODE SYSTEM TO BE REPAIRED/CORRECTED | | | TO COMPLY W/NEC 250. | | | |
|