| Plan Review Notes For Permit 15050702 |
| Permit Number |
15050702 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-02 18:53:03 | THE LOAD CALCS YOU SUBMITTED CALL FOR A 60KW GENERATOR, | | | YOUR SUBMITTAL PACKAGE REFLECTS A 48 KW UNIT. YOU WILL | | | NEED THE AUXILIARY TRANSFER SWITCH CONTACT KIT TO SHED | | | UNNECESSARY LOAD UNDER EMERGENCY CONDITIONS. |
|