| Plan Review Notes For Permit 15050700 |
| Permit Number |
15050700 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-02 17:25:23 | IMPORTANT NOTICE: | | | 1. BOAT LIFT MOTORS SHALL HAVE GFI PROTECTION PER NEC | | | 2108(C). | | | 2. TAKE VOLTAGE DROP & TEMPERATURE EXPOSURE INTO | | | ACCOUNT WHEN SIZING CONDUCTORS. | | | 3. CHECK OUTLETS IN DOCK PEDESTAL FOR COMPLIANCE W/NEC | | | 406.8 (WR RATED) | | | |
|