| 2015-08-13 11:44:13 | MECHANICAL APPROVED WITH EXCEPTION. |
| | 8/13/15 |
| | |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | 1) ACCESS PANELS REQUIRED FOR FIRE DAMPERS AT THE |
| | FIRE-RATED DORMITORY CORRIDOR/ASSEMBLY OCCUPANCY |
| | SEPARATION WALLS- SECTION 607.4 ACCESS AND |
| | IDENTIFICATION. |
| | FIRE AND SMOKE DAMPERS SHALL BE PROVIDED WITH AN |
| | APPROVED MEANS OF ACCESS, LARGE ENOUGH TO PERMIT |
| | INSPECTION AND MAINTENANCE OF THE DAMPER AND ITS |
| | OPERATING PARTS. THE ACCESS SHALL NOT AFFECT THE |
| | INTEGRITY OF FIRE-RESISTANCE-RATED ASSEMBLIES. THE |
| | ACCESS OPENINGS SHALL NOT REDUCE THE FIRE-RESISTANCE |
| | RATING OF THE ASSEMBLY. ACCESS POINTS SHALL BE |
| | PERMANENTLY IDENTIFIED ON THE EXTERIOR BY A LABEL |
| | HAVING LETTERS NOT LESS THAN 0.5 INCH (12.7 MM) IN |
| | HEIGHT READING: FIRE/SMOKE DAMPER, SMOKE DAMPER OR FIRE |
| | DAMPER. ACCESS DOORS IN DUCTS SHALL BE TIGHT FITTING |
| | AND SUITABLE FOR THE REQUIRED DUCT CONSTRUCTION. |
| | 2) PROVIDE A PRODUCT SAUBMITTAL PACKAGE THAT INCLUDES |
| | THE REVISED ENERGY CALCULATIONS, AND MANUFACTURER'S |
| | SPECIFICATIONS FOR THE AC UNITS, FIRE DAMPERS, |
| | MOTORIZED O/A DAMPERS, VAV BOXES, AND THE DUCT SMOKE |
| | DETECTORS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |