| 2015-08-11 12:16:06 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15050575 |
| | W. P. B. PERMIT: 14120580 |
| | ADD: 901 45TH ST. QUANTUM HOUSE |
| | CONT: HEDRICK BROTHERS |
| | TEL: ( 561)689-8880 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. AUG. 11/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. SHEET M1.1 SHOWS THE EAST WEST CORIDORS |
| | WITH FIRE DAMPERS AT THE FIRE RATED DORMITORY/ ASSEMBLY |
| | OCCUPANCY SEPARATION WALLS. PLEASE PROVIDE COMPLIANCE |
| | WITH THE 2010 FBC-B SECTION 716.4 ACCESS AND |
| | IDENTIFICATION. THIS SHOULD OCCUR AT ALL FIRE DAMPERS |
| | ON SITE. |
| | RESPONSE INDICATES SEE M5.1 DETAIL # 9. PLEASE NOTE |
| | THIS IS A WALL SECTION DETAIL OF A FIRE DAMPER LOCATED |
| | IN A RATED WALL. IR DOES NOT PROVIDE HOW YOU WILL GAIN |
| | ACCESS THROUGH A GYPSUM CEILING OR IDENTIFICATION FOR |
| | THE FIRE DAMPER. |
| | |
| | THE PRIME PERMIT # 14120580 SHEET 013-A1.5 AND SHEET |
| | 015-A1.7 NORTH PARTIAL CEILING PLAN SHOWS GYPSUM |
| | CEILINGS ON BOTH SIDES OF THE RATED WALL AND DOORWAY. |
| | THE DUCTWORK AND FIRE DAMPER ARE INSTALLED BETWEEN THE |
| | 2 CEILINGS. PLEASE ALSO SEE SHEET 025-A4.0 AND 026-A4.1 |
| | SHOW THE 2 DIFFERENT ELEVTIONS OF CEILINGS, THE UPPER |
| | CEILING RATED PER U. L. P531. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| 2015-08-11 12:02:56 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15050499 |
| | W. P. B. PERMIT: 14120580 |
| | ADD: 901 45TH ST. QUANTUM HOUSE |
| | CONT: HEDRICK BROTHERS |
| | TEL: ( 561)689-8880 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 24/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET M1.1 SHOWS THE EAST WEST CORIDORS WITH FIRE |
| | DAMPERS AT THE FIRE RATED DORMITORY/ ASSEMBLY OCCUPANCY |
| | WALLS. PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B |
| | SECTION 716.4 ACCESS AND IDENTIFICATION. THIS SHOULD |
| | OCCUR AT ALL FIRE DAMPERS ON SITE. |
| | |