| 2015-08-19 12:28:05 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | NOT ALL ITEMS PREVIOUSLY REQUESTED HAVE BEEN SUBMITTED. | | | I WILL NEED TO SEE THE RISER DIAGRAM AND LOAD CALCS FOR | | | THE RESPECTIVE PANELS. ACCORDING TO THE NOTES ON SHEET | | | E1, THE CONTRACTOR WILL PROVIDE THE RISER, BUT HE HAS | | | NOT DONE SO. | | | THEREFORE PER SAK, I WILL APPROVE THIS PERMIT AND THE | | | REQUIRED RISER DIAGRAM SHALL BE PROVIDED TO THE | | | INSPECTOR FOR FINAL INSPECTION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|