| 2015-07-06 15:34:30 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050569 |
| | ADD: 250 S. AUSTRALIAN AVE. |
| | CONT: EDD HELMS AIR CONDITIONING & ELEC. |
| | TEL: (305)653-2530 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 06/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEETS M1 & M3 BOTH SHOW THE REPLACEMENT OF THE |
| | CHILLER UNITS. THE PLANS DO NOT INDICATE HOW THE UNITS |
| | ARE GOING TO BE REMOVED AND REPLACED WITHOUT DAMAMGE TO |
| | THE BUILDING? WILL PORTIONS OF EITHER THE ROOF OR WALLS |
| | TO BE REMOVED AND REPLACED FOR THE REPLACEMENT OF |
| | UNITS? 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. PLEASE PROVIDE |
| | DETAILS. |
| | |
| | 2) SHEET M-3 SHOWS A WALL FIRE DAMPER BUT NOT A FIRE |
| | RATING IN ACCORDANCE WITH 2010 FBC-B 716.3.2 DAMPER |
| | RATING. TABLE 716.3.2.1. |
| | |
| | 3) SHEET M-2 INDICATES A NEW EXHAUST FAN EF-CR-1 WHAT |
| | APPEARS TO BE A NEW ROOF TOP EXHAUST FAN, PLEASE |
| | PROVIDE DETAILS OF THE NEW ROOF TOP PENETRATION. NEW |
| | ROOF TOP CURB AND PRODUCT APPROVALS FOR NEW ROOF TOP |
| | UNIT. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(G) PRE-ENGINEERED A/C STANDS ROOF TOP EXHAUST FANS |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) EXHAUST FANS TO COMPLY WITH 2010 FBC-B 1609.8 ROOF |
| | TOP STRUCTURES AND EQUIPMENT. |
| | |
| | 6) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | |
| | 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 6.2AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 6.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |