| 2015-06-02 14:24:43 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | | RESUBMITTED FOR A SECOND REVIEW: | | | | | | THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008 | | | EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE | | | APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA | | | BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND | | | FLORIDA BUILDING CODE ENERGY CONSERVATION. | | | 1. YOU SHALL SUBMIT AN ACTUAL CONNECTED LOAD CALC TO | | | ASCERTAIN THAT THE EXISTING SERVICE CAN ABSORB THE | | | ADDED LOADS. | | | 2. SUBMIT SPEC SHEET FOR THE PROPOSED CHARGING UNITS. | | | | | | FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT: | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | PH: (561) 805-6743 | | | EMAIL: [email protected] | | | |
|