| 2015-05-27 12:58:13 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) PLEASE REVISE THE INDEX OF DRAWINGS TO MATCH THE | | | PLAN SETS. | | | 2) THE PLANS SHALL BE SIGNED AND SEALED BY THE ENGINEER | | | OF RECORD- SECTION 105.3.1.2(5) WPB AMENDMENTS TO THE | | | FBC-10 BUILDING. | | | 3) SHEET R-2: INDICATE THE AMOUNT OF REFRIGERANT IN | | | EACH CIRCUIT SHOWN IN THE SCHEDULES- TABLE 1103.1 AND | | | SECTION 1104.2 FMC-10. IDENTIFY WHICH SYSTEMS ARE R22 | | | AND WHICH ARE R404A. | | | 4) SHEET S-2 INDICATES INSTALLATION OF NEW AC SYSTEMS: | | | PLEASE PROVIDE EQUIPMENT SCHEDULES ON THE PLAN AND | | | SUBMIT AC LOAD CALCULATIONS IN ACCORDANCE WITH ACCA | | | MANUAL N- SECTION 503.2.1 FBC-10 ENERGY. | | | 5) CONCERNING THE NEW AC UNITS: WILL NEW DS DETECTORS | | | BE INSTALLED. PROVIDE DETAILS ON THE PLANS IF | | | APPLICABLE. | | | 6) SHEET S-2 INDICATES A NEW ROOF HATCH. CLARIFY IF A | | | NEW ACCESS LADDER IS BEING INSTALLED AND PROVIDE | | | DETAILS IF APPLICABLE PER SECTION 306.5 FMC-10. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|