2015-05-27 12:58:131ST REVIEW: FBC 2010 MECHANICAL
  
 1) PLEASE REVISE THE INDEX OF DRAWINGS TO MATCH THE
 PLAN SETS.
 2) THE PLANS SHALL BE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD- SECTION 105.3.1.2(5) WPB AMENDMENTS TO THE
 FBC-10 BUILDING.
 3) SHEET R-2: INDICATE THE AMOUNT OF REFRIGERANT IN
 EACH CIRCUIT SHOWN IN THE SCHEDULES- TABLE 1103.1 AND
 SECTION 1104.2 FMC-10. IDENTIFY WHICH SYSTEMS ARE R22
 AND WHICH ARE R404A.
 4) SHEET S-2 INDICATES INSTALLATION OF NEW AC SYSTEMS:
 PLEASE PROVIDE EQUIPMENT SCHEDULES ON THE PLAN AND
 SUBMIT AC LOAD CALCULATIONS IN ACCORDANCE WITH ACCA
 MANUAL N- SECTION 503.2.1 FBC-10 ENERGY.
 5) CONCERNING THE NEW AC UNITS: WILL NEW DS DETECTORS
 BE INSTALLED. PROVIDE DETAILS ON THE PLANS IF
 APPLICABLE.
 6) SHEET S-2 INDICATES A NEW ROOF HATCH. CLARIFY IF A
 NEW ACCESS LADDER IS BEING INSTALLED AND PROVIDE
 DETAILS IF APPLICABLE PER SECTION 306.5 FMC-10.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER