Plan Review Notes
Plan Review Notes For Permit 15050530
Permit Number 15050530
Review Stop M
Sequence Number 2
Notes
Date Text
2015-07-13 11:10:16PERMIT #15050530
 500 BELVEDERE RD.
 7/13/15
  
 PROVISOS: THE RE-SUBMITTED PLANS WERE RETURNED WITHOUT
 ADDRESSING ALL 1ST REVIEW COMMENTS. I AM APPROVING THE
 PLANS WITH EXCEPTION, HOWEVER REVISIONS TO THE
 PERMITTED PLANS ARE REQUIRED. PLEASE PROVIDE:
 1) SHEET R8: ENLARGED MECHANICAL CENTER LAYOUT PLANS
 IDENTIFYING ALL COMPONENTS OF THE STRUCTURE, AND
 EQUIPMENT CONTAINED WITHIN.
 2) UPDATED SHOP DRAWINGS FOR THE MECHANICAL CENTER TO
 MEET THE CURRENT WIND LOAD DESIGN CRITERIA IN
 ACCORDANCE WITH SECTION1609 FLORIDA BUILDING CODE 2010.
 THE DRAWINGS SHALL BE REVIEWED AND APPROVED BY THE
 ARCHITECT OF RECORD.
 3) CERTIFICATION OR OTHER DOCUMENTATION TO VERIFY
 INSPECTION APPROVAL OF THE PRE-MANUFACTURED CENTER.
 4) MECHANICAL CENTER VENTILATION DETAILS AND
 CALCULATIONS VERIFYING COMPLIANCE WITH SECTIONS
 1105.5.6.3 FBC-10 MECHANICAL FOR NORMAL OPERATION, AND
 1105.6.4 FOR EMERGENCY CONDITIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved