| Plan Review Notes For Permit 15050530 |
| Permit Number |
15050530 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-13 11:10:16 | PERMIT #15050530 | | | 500 BELVEDERE RD. | | | 7/13/15 | | | | | | PROVISOS: THE RE-SUBMITTED PLANS WERE RETURNED WITHOUT | | | ADDRESSING ALL 1ST REVIEW COMMENTS. I AM APPROVING THE | | | PLANS WITH EXCEPTION, HOWEVER REVISIONS TO THE | | | PERMITTED PLANS ARE REQUIRED. PLEASE PROVIDE: | | | 1) SHEET R8: ENLARGED MECHANICAL CENTER LAYOUT PLANS | | | IDENTIFYING ALL COMPONENTS OF THE STRUCTURE, AND | | | EQUIPMENT CONTAINED WITHIN. | | | 2) UPDATED SHOP DRAWINGS FOR THE MECHANICAL CENTER TO | | | MEET THE CURRENT WIND LOAD DESIGN CRITERIA IN | | | ACCORDANCE WITH SECTION1609 FLORIDA BUILDING CODE 2010. | | | THE DRAWINGS SHALL BE REVIEWED AND APPROVED BY THE | | | ARCHITECT OF RECORD. | | | 3) CERTIFICATION OR OTHER DOCUMENTATION TO VERIFY | | | INSPECTION APPROVAL OF THE PRE-MANUFACTURED CENTER. | | | 4) MECHANICAL CENTER VENTILATION DETAILS AND | | | CALCULATIONS VERIFYING COMPLIANCE WITH SECTIONS | | | 1105.5.6.3 FBC-10 MECHANICAL FOR NORMAL OPERATION, AND | | | 1105.6.4 FOR EMERGENCY CONDITIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|