Plan Review Notes
Plan Review Notes For Permit 15050530
Permit Number 15050530
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-27 08:42:291ST REVIEW: FBC 2010 MECHANICAL
  
 1) ALL PLANS , INCLUDING SHEETS A-1 AND EQ-1, SHALL BE
 SIGNED AND SEALED BY THE ENGINEER OF RECORD- SECTION
 105.3.1.2(5) WPB AMENDMENTS TO THE FBC-10 BUILDING.
 2) SHEETS R-1& R-3: INDICATE THE DISCHARGE OR
 TERMINATION LOCATIONS OF THE CONDENSATE PIPING FROM ALL
 COMPONENTS OF THE REFRIGERATION SYSTEMS INCLUDING THE
 WALK-IN BOXES, CASES, CONDENSERS, CHILLERS, ETC. PLEASE
 NOTE THAT CONDENSATE FROM COOLING COILS IS PROHIBITED
 TO DISCHARGE INTO THE SANITARY SYSTEM PER SEC. 90-126
 WPB CODE OF ORDINANCES.
 3) SHEET R-2: INDICATE THE AMOUNT OF REFRIGERANT IN
 EACH CIRCUIT SHOWN IN THE SCHEDULES- TABLE 1103.1 AND
 SECTION 1104.2 FMC-10.
 4) SHEET R-8: THE REFRIGERATION ROOF PLAN DETAIL, AND
 THE MECHANICAL CENTER DIAGRAM ON THE SHEET NEED TO BE
 ENLARGED FOR CLARITY: PLEASE COMPLY.
 5) SHEET R-8: PLEASE REVIEW AND UPDATE THE WIND LOAD
 DESIGN CRITERIA FOR THE MECHANICAL CENTER TO 170 MPH
 PER SECTION 1609 FBC-10 BUILDING.
 6) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE
 CONDENSERS AND MECHANICAL CENTER TO THE MAIN STRUCTURE-
 SECTION 301.12 FMC-10. SUBMIT NOA?S OR FL. PRODUCT
 APPROVALS FOR THE ROOF STANDS.
 7) PROVIDE THE EFFICIENCY RATINGS FOR CHILLERS 1 & 2-
 TABLE 503.2.3(7) FBC-10 ENERGY CONSERVATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  