2015-07-13 10:15:34PUBLIX REFRIGERATION
 PERMIT #15050527
 831 VILLAGE BLVD
 7/13/15
  
 PROVISOS: THE RE-SUBMITTED PLANS WERE RETURNED WITHOUT
 ADDRESSING ALL 1ST REVIEW COMMENTS. I AM APPROVING THE
 PLANS WITH EXCEPTION, HOWEVER REVISIONS TO THE
 PERMITTED PLANS ARE REQUIRED. PLEASE PROVIDE:
  
 1) SHEET R8: ENLARGED MECHANICAL CENTER LAYOUT PLANS
 IDENTIFYING ALL COMPONENTS OF THE STRUCTURE, AND
 EQUIPMENT CONTAINED WITHIN.
 2) UPDATED SHOP DRAWINGS FOR THE MECHANICAL CENTER TO
 MEET THE CURRENT WIND LOAD DESIGN CRITERIA IN
 ACCORDANCE WITH SECTION1609 FLORIDA BUILDING CODE 2010.
 THE DRAWINGS SHALL BE REVIEWED AND APPROVED BY THE
 ARCHITECT OF RECORD.
 3) CERTIFICATION OR OTHER DOCUMENTATION TO VERIFY
 INSPECTION APPROVAL OF THE PRE-MANUFACTURED CENTER.
 4) SEQUENCE OF OPERATION FOR THE REFRIGERANT LEAK
 DETECTOR IN THE MECHANICAL CENTER, AND A SUBMITTAL FOR
 THE DEVICE REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD.
  