| 2015-05-27 14:31:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THE OCCUPANY IS NOT CLEARLY INDICATED; |
| | STORE/COMMERCIAL IS GENERAL AND VAGUE. PLEASE PROVIDE |
| | EXISTING AND PROPOSED OCCUPANCY PER NFPA 101. |
| | |
| | 2) A LIFE SAFETY PALN IS NOT PROVIDED. COMPLETE LIFE |
| | SAFETY PLANS FOR EACH OCCUPANCY SHALL BE PROVIDED THAT |
| | ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON |
| | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| | AND EQUIPMENT. |
| | |
| | 3) THE FIRE WALL DOES NOT INDICATE A FIRE RATING. A 2HR |
| | FIRE RATING IS REQUIRED WITH FIRE WALL DETAIL DRAWINGS, |
| | INCLUDING LISTED SEALED OPENINGS. |
| | |
| | 4) NO DIMENSIONS ARE INDICATED. PLEASE INDICATED ALL |
| | DIMENSIONS ON THE RESUBMITTAL. |
| | |
| | 5) EXIT DOOR HARDWARE IS NOT INDICATED. DOORS SHALL BE |
| | ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE |
| | WHENEVER THE BUILDING IS OCCUPIED. LOCKS, IF PROVIDED, |
| | SHALL NOT REQUIRE THE USE OF A KEY, TOOL, OR SPECIAL |
| | KNOWLEDGE OR EFFORT FOR OPERATION FROM THE EGRESS SIDE. |
| | |
| | INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY |
| | LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A |
| | LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE |
| | RELEASED FROM THE EGRESS SIDE OF THE DOOR. |
| | |
| | PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING |
| | MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT |
| | MORE THAN ONE RELEASING OPERATION. THE RELEASING |
| | MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. |
| | THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING |
| | OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT |
| | GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO |
| | OPERATE. |
| | |
| | A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY |
| | DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS |
| | PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH |
| | LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE |
| | DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO |
| | OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED. |
| | |
| | THUMB-TURN LOCK WHEN EQUIPPED ON OTHER DOORS IS SHALL |
| | BE INSTALED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW |
| | (SUCH AS ADAMS RITE 4089 OR SIMILAR). |
| | |