| Plan Review Notes For Permit 15050499 |
| Permit Number |
15050499 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-09 13:43:23 | 15050499 | | | 3234 S. DIXIE HWY | | | COMMERCIAL REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | ON THE PANEL SCHEDULE INCLUDE THE SHOW WINDOW LIGHTING | | | AND SIGN CIRCUIT. PROVIDE SHOW WINDOW LIGHTING OUTLETS. | | | NEC 210.62, 408.4, 600.5 | | | | | | PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO | | | THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS | | | PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY | | | CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. VERIFY THE | | | LIGHTING AND SIGN TIME CLOCKS HAVE BATTERY BACKUP. FBC | | | ENERGY CONSERVATION 505.2 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN | | | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY | | | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; | | | 505.5.3; T. 505.5.3 | | | | | | PROVIDE SPECIFICATIONS/DETAIL FOR FIRESTOPPING THE | | | RECEPTACLES ON THE NEW FIREWALL SEPERATION. NEC 300.21 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | |
|