| 2015-06-24 11:42:14 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15050499 |
| | ADD: 3234 S. DIXIE HWY. |
| | L. B. ROWE |
| | TEL: (561)635-8227 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 24/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 DOES NOT INDICATE UNDER THE 2010 EXISTING |
| | BUILDING CODE TO WHAT COMPLIANCE METHOD THE PLANS WERE |
| | DESIGNED/ |
| | |
| | 2) THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE |
| | SPRINKLERED OR NOT. 107.3.5.1.1 MINIMUM COMMERCIAL |
| | BUILDING PLAN REVIEW CRITERIA. |
| | |
| | 3) THE PLANS INDICATE SPLITTING ONE TENANT SPACE AND |
| | CREATING TWO TENANT SPACES. THE PLANS DO NOT PROVIDE |
| | WHAT DESIGN THE TENANT SEPARATION WALL WILL BE DESIGNED |
| | TOO? 2010 FBC-B 709.1.6. PLEASE PROVIDE DETAIL OF THE |
| | TENANT SEPARATION WALL. |
| | |
| | 4) SHEET A1 INDICATES THERE IS TO BE REPLACEMENT |
| | WINDOWS AND DOORS. PLEASE PROVIDE THE WIND DESIGN |
| | CRITERIA FOR THIS LOCATION. |
| | WIND DESIGN CRITERIA |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 5) PLEASE PROVIDE THE MISSING PRODUCT APPROVALS TO |
| | COMPLY WITH: 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) STOREFRONTS |
| | |
| | 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) PLEASE NOTE IF THIS IS A NON-SPRINKLERED BUILDING |
| | THE COMMON PATH OF TRAVEL IS 75 FEET FOR BUSINESS AND |
| | MERCANTILE OCCUPANCIES. |
| | 2010 FBC-B 1014.3. THE TENANCY IN 3234 DOES NOT HAVE A |
| | REAR DOOR MAKING THE TRAVEL DISTANCE OVER 75 FEET. THIS |
| | WILL REQUIRE A SECOND MEANS OF EGRESS TO COMPLY WITH |
| | FBC-B 1014.3. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |