| Plan Review Notes For Permit 15050498 |
| Permit Number |
15050498 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-15 10:29:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC 107, TWO COMPLTE COLLATED SETS OF DOCUMENTS | | | REQUIRED FOR PERMIT ISSUANCE. | | | | | | 2. PROVIDE A COPY OF THE CONTRACT (AND MATERIAL | | | RECEIPTS, IF APPLICABLE) FOR THIS JOB. VALUE TO INCLUDE | | | THE VALUE OF LABOR, MATERIALS, OVERHEAD, PROFIT, EVEN | | | IF PROVIDED BY OTHERS, FBC 109. | | | | | | 3. PRODUCTS PROPOSED ARE NOT CLEAR. THE STC AND IIC | | | TESTS ARE FOR "QEP PREMIUM 6MM CORK UNDERLAYMENT | | | #72000", FLAME SPREAD IS FOR "BADGER CORK". APPLICATION | | | SCOPE STATES "FLOOR REPLACEMENT" AND DOES NOT STATE | | | TYPE OF FLOOR AND PROPOSED INSTALLATION METHOD. THIS IS | | | TYPICALLY INCLUDED IN THE PERMIT DESCRIPTION BUT CAN BE | | | DONE ON A FLOOR PLAN, FBC 107. | | | | | | 4. SCOPE NOT CLEAR. SQUARE FOOT AREA, AREAS AFFECTED | | | NOT INDICATED. THIS IS TO BE DESCRIBED EITHER IN THE | | | PERMIT DESCRIPTION OR ON A PLAN, FBC 107. | | | | | | | | | |
|