| Plan Review Notes For Permit 15050486 |
| Permit Number |
15050486 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-14 07:01:31 | 1) SUBMIT A RISER FOR THE ROOF DRAIN. SHOW THE PIPE | | | SIZE OF THE VERTICAL LEADER AND THE HORIZONTAL DRAIN | | | PIPE. PIPE SIZES SHALL COMPLY W/ 2010 FBC-PLUMBING, | | | TABLE 1106.2 (1), TABLE 1106.3. INDICATE ON THE PLAN | | | THE SQUARE FOOTAGE OF THE ROOF THAT IS DRAINING INTO | | | THE ROOF DRAIN. | | | 2) SUBMIT DETAILS AND CALCULATIONS FOR ROOF DRAINAGE OF | | | NON-SLOPED ROOF AREAS AND ALSO SECONDARY (EMERGENCY) | | | DRAINAGE OF THESE ROOF AREAS. 2010 FBC-R, SECS.R903.4, | | | R903.4.1. | | | 3) SHT. P.0 - NOTE #1 - DELETE THE REFERENCE TO 2001 | | | FBC. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|